Description

The Universal Refrigerant Detection System is for systems that use A2L refrigerants. A2L refrigerants are mildly flammable and require mitigation controls to check for leaks. In the event of a refrigerant leak, the ICM-UA2L-24C-DUAL provides rapid-response compressor lockout and activates the system fan as well triggers an alarm. Compared to other refrigerant detection systems, the ICM-UA2L-24C-DUAL is designed specifically for use with the more prominent A2L refrigerants (R32 and R454B) being used today. It has a dual channel design allowing for coverage across multiple zones, detects and responds to leak detection and integrates into your HVAC control boards, Building Management System (BMS) /Modbus without add-ons. This integrations allows you to monitor you refrigerant levels remotely, log events as well as get alerts. The ICM-UA2L-24C-DUAL is not a portable detection sensor. Features:

  • Fault Monitoring
  • Status, Power LED Indicators
  • Dry Contact Fan Output (N.C.) and Alarm Output (N.O.)
  • Dry Contact CC Output
  • MODBUS Communication to A2L Refrigerant Sensor
  • Common 1/4” Quick Connect Terminations
  • Support multiple leak detection sensors
  • Open-board with standoffs or plastic-enclosed assembly

Inputs:

  • Working voltage: 24 VAC, 50/60 Hz Input (SELV/Class 2)
  • Frequency: 50/60 Hz

Outputs:

  • 80mA @ 5VDC per RS-485 port maximum
  • K1: Dry Contact SPST
    • NO: CC Output; Class 2, 100VA (Nominal 2.5A @ 24V)
  • K2: Dry Contact SPDT
    • NC: Fan output; Class 2, 100VA (Nominal 4A @ 24V)
    • NO: Alarm signal; Class 2, 100VA (Nominal 4A @ 24V)

Environment:

  • Operating Temperature: -40°C to 70°C
  • Storage Temperature: -40°C to 85°C (not powered)
  • Relative Humidity: 0-95% RH
  • Pollution Degree: 2

Dimensions:

  • Length: 2.75″l x 4″w
  • Wire Harness: 6ft terminated wire harness

The ICM-UA2L-24C-DUAL is an indispensable tool for detecting and responding to R32 and R454B refrigerant leaks in your equipment.